Refrigerant leak rate calculator

For the EPA leak repair rules in effect since January 1, 2026: 40 CFR 84.106 (HFC appliances, 15 lb or more) and 40 CFR 82.157 (Section 608, CFC and HCFC appliances, 50 lb or more). Enter the top-offs, get the leak rate and every deadline.

Method used at this site
Refrigerant added (all top-offs, oldest first is fine)
More options

Do this for every appliance, automatically

LeakLedger for iPhone and iPad keeps the history per appliance, opens leak cases, reminds you before each deadline and exports audit-ready PDFs.

Get early access

How the leak rate is calculated

EPA defines the leak rate as the percentage of the full charge that would be lost over 12 months if the current rate of loss continued (40 CFR 84.102). Owners and operators must calculate it every time refrigerant is added, with a few exceptions such as additions right after a retrofit, at installation, or seasonal variance.

Annualizing method

leak rate % = (lb added / full charge) / (min(days since last addition, 365) / 365) x 100

Example: a 60 lb walk-in freezer gets 3 lb, then another 3 lb 30 days later. The second calculation is 3 / 60 / (30 / 365) x 100 = 60.83%, well over the 20% commercial refrigeration threshold.

Rolling average method

leak rate % = (lb added in the last 365 days / full charge) x 100

If a successful follow-up verification test showed the leaks were repaired less than a year ago, only additions after that test count.

First calculation in 2026

For the first calculation after January 1, 2026 under Part 84, the annualizing method uses 365 days and the rolling average method counts only pounds added since January 1, 2026 (84.106(b)).

Thresholds and deadlines

ApplianceThresholdRule
Commercial refrigeration20%84.106(c)(2)(i), 82.157(c)(2)(i)
Industrial process refrigeration30%84.106(c)(2)(ii), 82.157(c)(2)(ii)
Comfort cooling, refrigerated transport, other10%84.106(c)(2)(iii), 82.157(c)(2)(iii)

Over the threshold: identify and repair leaks within 30 days (120 days if an industrial process shutdown is required), do the initial verification test within the same window, and the follow-up verification test within 10 days of a successful initial test. Appliances that leak 125% or more of their full charge in a calendar year must be reported to EPA by March 1 of the following year.

Read the full guide: EPA AIM Act leak repair rules for 2026, explained for technicians.

This calculator is a recordkeeping aid, not legal advice. It uses the formulas in 40 CFR 84.102 and 82.152 as published on eCFR in September 2026. Check the current regulations for your situation. LeakLedger is not affiliated with or endorsed by the U.S. EPA.